Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
.

3.2.16 RB2000 (Message Type R) Description

RB2000
SIA Mode Description
Example
<LF><CRC><R><sequence#><receiver#><line#>[<VDS message>]<CR>
Table 69: RB2000 (Message Type R) Byte Description
Title
LF
CRC
R
sequence#
Receiver#
line#
<VDS message>
CR
Figure 19: Single message sent to Printer
MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx
+++ RB2000_EVENT_RAW_DATA
Figure 20: Multiple messages sent to printer
MM/DD HH:MM Lxx RB2 ACCT xxxxxxxxxxxx
+++ RB2000_EVENT_RAW_DATA 1
+++ RB2000_EVENT_RAW_DATA 2
...
+++ RB2000_EVENT_RAW_DATA n
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
Description
Standard line feed character, hex 0A.
Cyclical redundancy check number.
ASCII R, Message Type R for RB2000 format.
The message sequence number. The valid sequence number range: 0001
to 9999.
The receiver gateway that sent the message. Valid digits: 01 to 99 for the
D6600.
The line number of the line in the receiver gateway that sent the message.
Valid digits: 00 to 99. The receiver uses Line 0 (zero) for internal
messages.
VDS message sent as a hex string, the receiver extracts the alarm type.
Hex 0D