Ademco 4-2 Express (Message Type C) - Bosch Conettix D6600 Manual

Computer interface of receiver/gateway
Table of Contents

Advertisement

Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
3.2.5

Ademco 4-2 Express (Message Type c)

4-2 Express
SIA Mode Description
Example
<LF><CRC><c><sequence#><receiver#><line#>[#aaaa|XY]<CR>
Table 49: Ademco 4-2 Express (Message Type c) Byte Description
Title
LF
CRC
Message Type
sequence#
receiver#
line#
(Line/Group #)
account#
XY
Figure 11: Message sent to printer
mm/ddshh:mmsLxxsE42sACCTsaaaasEVENT=XY
For lines that are grouped, Gxx appears instead of Lxx.
Table 50: Ademco 4-2 Express (Message Type c) Printer Output
Characters
Description
E42
Ademco 4-2 Express format.
Lxx:
Line number.
Gxx
Grouped line numbers.
48
Bosch Security Systems | 2012.09 | 4998122703-05
Description
Standard line feed character.
Cyclical redundancy check number.
c
The message sequence number. The valid sequence number range is
0001 to 9999.
The receiver gateway that sent the message. Valid digits are 01 to 99 for
the D6600/D6100/D6100IPv6.
The line number of the line in the receiver gateway that sent the
message. Valid digits are 00 to 99. The receiver uses Line 0 (zero) for
internal messages.
The communicator's account number has four digits.
Event code and Zone number.