Silent Knight Fsk2 (Message Type M) - Bosch Conettix D6600 Manual

Computer interface of receiver/gateway
Table of Contents

Advertisement

Conettix D6600/D6100IPv6/D6100i | Computer Interface Manual | 3.0 Computer Communication
Protocols
.

3.1.25 Silent Knight FSK2 (Message Type m)

Silent Knight
D6500 Byte Description
FSK2 Example
1
2
h
m
Table 32: Silent Knight FSK2 (Message Type m) Byte Description
#
Title
1
Header
Character (h)
2
Message Type
3-4
Receiver
Number
5
Line/Group
Number
6
Spaces
7-14
Account
Number
15
"
16-19
EEZZ
20
"
21
***
22
Trailer
Character
Bosch Security Systems, Inc. | 2012.09 | 4998122703-05
3
4
5
6
7
8
r
r
l
s
a
a
Description
Optional. Check with the computer automation software for
compatibility.
m
Receiver gateway number from 01 to 99.
Line number in the receiver gateway that sent the message.
One space.
Maximum eight-digit account code. If the account code is less than
eight digits, enter the actual number of digits without a leading space.
Separator.
First event and zone number. If this is the only event, it will be ended
with the terminator. Up to eight reports. One report has four digits:
one-digit event code, one-digit condition code, two-digit zone code.
Separator.
Next data.
Typically, HEX 14.
9
10 11 12 13 14 15 16 17 18 19 20 21 22
a
a
a
a
a
a
"
E
E
Z
Z
"
*** t
35