Table 8- 1
Parameter
p1155
p2200
p2253
p2263
p2264
p2280
p2285
Function diagrams (see SINAMICS S120/S150 List Manual)
• 7950
• 7951
• 7954
• 7958
• 7959
• 7960
Overview of important parameters (see SINAMICS S120/S150 List Manual)
Fixed setpoints
• p2201[0...n]
...
• p2215[0...n]
• p2220[0...n]
• p2221[0...n]
• p2222[0...n]
• p2223[0...n]
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Important parameters for the level control
Designation
CI: Speed controller, speed set-
point 1
BI: Technology controller enable
CI: Technology controller setpoint
1
Technology controller type
CI: Technology controller actual
value (X
)
ACTUAL
Technology controller p-gain
Technology controller integral time p2285 Determine by optimization
Technology controller - Fixed values, binary selection (r0108.16 = 1 and
p2216 = 2)
Technology controller - Fixed values, direct selection (r0108.16 = 1 and
p2216 = 1)
Technology controller - Motorized potentiometer (r0108.16 = 1)
Technology controller - Closed-loop control (r0108.16 = 1)
Technology controller - Kp/Tn adaption (r0108.16 = 1)
Technology controller - Controller DC link voltage (r0108.16 = 1)
CO: Technology controller fixed value 1
CO: Technology controller fixed value 15
BI: Technology controller fixed value selection bit 0
BI: Technology controller fixed value selection bit 1
BI: Technology controller fixed value selection bit 2
BI: Technology controller fixed value selection bit 3
8.1 Technology controller
Example
p1155 = r2294 Tec_ctrl output_sig [3080]
p2200 = 1 Technology controller enabled
p2253 = r2224 Fixed setpoint active [7950]
p2263 = 1 D component in fault signal [7958]
p2264 = r4055 [1] Analog input AI1 of TB30
p2280 Determine by optimization