Controllers: Protocol always "SIMATIC S7 - 300/400"
Table 11- 8
Field
Network parameter profile
Network parameter baud rate
Communication partner address
Communication partner
slot/rack
Table 11- 9
Field
Name
Controller
Type
Area
DB
(data block number)
DBB, DBW, DBD
(data block offset)
Length
Acquisition cycle
Number of elements
Decimal places
Note
• You can operate a SIMATIC HMI together with a drive unit independently of an existing
controller.
A basic "point-to-point" connection can only be established between two nodes (devices).
• The "variable" HMI function can be used for drive units. Other functions cannot be used
(e.g. "messages" or "recipes").
• Individual parameter values can be accessed. Entire arrays, descriptions, or texts cannot
be accessed.
Drive functions
Function Manual, 11/2017, 6SL3097-4AB00-0BP5
Additional parameters
Variables: "General" tab
11.2 Communication via PROFIBUS DP
Value
DP
Any
PROFIBUS address of the drive unit
Don't care, 0
Value
Any
Any
Depending on the addressed parameter value,
e.g.:
INT: for integer 16
DINT: for integer 32
WORD: for unsigned 16
REAL: for float
DB
Parameter number
1 ... 65535
Drive object No. and sub-index
bit 15 ... 10: Drive object No. 0 ... 63
bit 9 ... 0: Sub-index 0 ... 1023
or expressed differently
DBW = 1024 * drive object No. + sub-index
Not activated
Any
1
Any
Communication
785