Siemens Sinamics G120P Operating Instructions Manual page 449

Converter cabinet units 110 kw - 400 kw
Hide thumbs Also See for Sinamics G120P:
Table of Contents

Advertisement

Number
Cause
A07921
Torque/speed too high
A07922
Torque/speed out of tolerance
F07923
Torque/speed too low
F07924
Torque/speed too high
A07927
DC braking active
A07980
Rotary measurement activated
A07981
No enabling for rotary measure-
ment
A07991
Motor identification activated
F08501
PROFINET: Setpoint timeout
F08502
PROFINET: Monitoring time, sign-
of-life expired
F08510
PROFINET: Send configuration
data not valid
A08511
PROFINET: Receive configuration
data not valid
A08526
PROFINET: No cyclic connection
A08565
PROFINET: Consistency error
affecting adjustable parameters
F08700
CAN: Communications error
A8800
PROFIenergy energy-saving mode
active
F13100
Know-how protection: Copy protec-
tion error
F13101
Know-how protection: Copy protec-
tion cannot be activated
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Remedy
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Check the connection between the motor and the load.
Adapt the parameterization corresponding to the load.
Not required
Not required
Acknowledge pending faults.
Establish missing enables (see r00002, r0046).
Switch on the motor and identify the motor data.
Check the PROFINET connection.
Set the controller into the RUN mode.
If the fault occurs repeatedly, check the monitoring time set p2044.
Check the PROFINET connection.
Check the PROFINET configuration
Activate the controller with cyclic operation.
Check the parameters "Name of Station" and "IP of Station" (r61000,
r61001).
Check the following:
IP address, subnet mask or default gateway is not correct.
IP address or station name used twice in the network.
Station name contains invalid characters.
A CAN communications error has occurred. Check the following:
Bus cable
Baud rate (p8622)
Bit timing (p8623)
Master
Start the CAN controller manually with p8608 = 1 after the cause of the
fault has been resolved!
Not required
The know-how protection and the copy protection for the memory card
are active. An error occurred when checking the memory card.
Insert a suitable memory card and switch the inverter supply voltage
temporarily off and then on again (POWER ON).
Deactivate the copy protection (p7765).
Insert a valid memory card.
Alarms, faults and system messages
9.5 List of alarms and faults
449