Alarms, faults and system messages
9.5 List of alarms and faults
Number
Cause
F07801
Motor overcurrent
A07805
Drive: Power unit overload I2t
F07806
Regenerative power limit exceeded Increase the deceleration ramp.
F07807
Short-circuit detected
A07850
External alarm 1 ... 3
A07851
A07852
F07860
External fault 1 ... 3
F07861
F07862
F07900
Motor blocked
F07901
Motor overspeed
F07902
Motor stalled
A07903
Motor speed deviation
A07910
Motor overtemperature
A07920
Torque/speed too low
448
Remedy
Check the current limits (p0640).
Vector control: Check the current controller (p1715, p1717).
V/f control: Check the current limiting controller (p1340 ... p1346).
Increase the acceleration ramp (p1120) or reduce the load.
Check the motor and motor cables for short-circuit and ground fault.
Check the motor regarding the star/delta connection and type plate pa-
rameterization.
Check the power unit / motor combination.
Select the flying restart function (p1200) if switched to rotating motor.
Reduce the continuous load.
Adapt the load cycle.
Check the assignment of rated currents of the motor and power unit.
Reduce the driving load.
Use a power unit with higher energy recovery capability.
For vector control, the regenerative power limit in p1531 can be reduced
until the fault is no longer activated.
Check the inverter connection on the motor side for any phase-phase
short-circuit.
Rule out that line and motor cables have been interchanged.
The signal for "external alarm 1" has been triggered.
Parameters p2112, p2116 and p2117 determine the signal sources for
the external alarm 1... 3.
Remedy: Remove the causes of these alarms.
Remove the external causes for this fault.
Check that the motor can run freely.
Check the torque limits (r1538 and r1539).
Check the parameters of the "Motor blocked" message (p2175, p2177).
Activate the precontrol for the speed limiting controller (p1401 bit 7 = 1).
Increase the hysteresis for overspeed signal p2162.
Check whether the motor data has been set correctly and perform a mo-
tor identification.
Check the current limits (p0640, r0067, r0289). If the current limits are too
low, the drive cannot be magnetized.
Check whether motor cables are disconnected during operation.
Increase p2163 and/or p2166.
Increase the torque, current and power limits.
Check the motor load.
Check the motor's ambient temperature.
Check the KTY84 sensor.
Check the overtemperatures of the thermal model (p0626 ... p0628).
The torque deviates from the torque/speed envelope curve.
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A