Parameter contents
Parameter contents can be parameter values or connector parameters. You require two
words for connector parameters. For interconnecting connector parameters refer to BICO
technology: Interconnecting signals (Page 174).
Enter the parameter value in the parameter channel right-justified as follows:
• 8-bit values:
• 16-bit values:
• 32-bit values:
Enter a connector parameter right-justified as follows:
• Number of the connector parameter:
• Drive object of the connector parameter:
• The index or bit field number of the connector parameter: Low word, bits 0 ... 9
Telegram examples, length of the parameter channel = 4
Read request: Read out serial number of the Power Module (r7841[2])
To obtain the value of the indexed parameter r7841, you must fill the telegram of the
parameter channel with the following data:
● PKE, bit 12 ... 15 (AK): = 6 (request parameter value (field))
● PKE, bit 0 ... 10 (PNU): = 1841 (parameter number without offset)
Parameter number = PNU + offset (page index)
(7841 = 1841 + 6000)
● IND, bit 8 ... 15 (page index): = 90 hex (offset 6000 ≙ 90 hex)
● IND, bit 0 ... 7 (subindex): = 2 (index of the parameter)
● Because you want to read the parameter value, words 3 and 4 in the parameter channel
for requesting the parameter value are irrelevant. They should be assigned a value of 0,
for example.
Figure 6-15
Telegram for a read request from r7841[2]
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
Low word, bit 0 ... 7,
bits 8 ... 15 are zero.
Low word, bits 0 ... 15,
Low word and high word
Operation
6.8 Communication via RS485
High word
Low word, bits 10 ... 15
225