Functions
7.3 Setpoints
7.3.1
Analog input as setpoint source
Interconnecting an analog input
If you have selected a pre-assignment without a function of the analog input, then you must
interconnect the parameter of the main setpoint with an analog input.
Figure 7-8
Table 7- 7
Parameter
p1070 = 755[0]
p1075 = 755[0]
You must adapt the analog input to the connected signal, e.g. ± 10 V or 4 ... 20 mA.
7.3.2
Specifying the setpoint via the fieldbus
Interconnecting the fieldbus with the main setpoint
Figure 7-9
Most standard telegrams receive the speed setpoint as a second process data PZD2.
Table 7- 8
Parameter
p1070 = 2050[1]
p1075 = 2050[1]
344
Example: Analog input 0 as setpoint source
Setting with analog input 0 as setpoint source
Remark
Main setpoint
Interconnects the main setpoint with analog input 0
Additional setpoint
Interconnects the additional setpoint with analog input 0
Fieldbus as setpoint source
Setting the fieldbus as setpoint source
Remark
Main setpoint
Interconnects the main setpoint with process data PZD2 from the fieldbus.
Additional setpoint
Interconnects the additional setpoint with process data PZD2 from the fieldbus.