Offset and page index of the parameter numbers
Parameter numbers < 2000
Parameter numbers ≥ 2000
Parameter number
0000 ... 1999
2000 ... 3999
6000 ... 7999
8000 ... 9999
10000 ... 11999
20000 ... 21999
30000 ... 31999
60000 ... 61999
Indexed parameters
For indexed parameters, you must write the index as hex value into the subindex (IND
bit 15 ... 8).
Parameter contents
Parameter contents can be parameter values or connector parameters. For interconnecting
connector parameters refer to BICO technology: Interconnecting signals (Page 174).
Enter the parameter value, right-justified, as follows in the 4th word of the parameter
channel:
• 8-bit values:
• 16-bit values: 4th word, bits 0 ... 15,
• 32-bit values: 3rd and 4th word
Enter a connector parameter as follows:
• Number of the connector parameter:
• Drive object of the connector parameter:
• The index or bit field number of the connector parameter:
Inverter cabinet units
Operating Instructions, 12/2014, A5E32923362A
6.5 PROFIdrive profile for PROFIBUS and PROFINET
PNU = parameter number.
Write the parameter number into the PNU (PKE bit 10 ... 0).
PNU = parameter number - offset.
Write the parameter number minus the offset into the PNU
(PKE bit 10 ... 0).
Write the offset in the page index (IND bit 7 ... 0).
Offset
Page index
Hex
Bit 7
0
0 hex
0
2000
80 hex
1
6000
90 hex
1
8000
20 hex
0
10000
A0 hex
1
20000
50 hex
0
30000
F0 hex
1
60000
74 hex
0
4th word, bit 0 ... 7,
bits 8 ... 15 of the 4th word and the 3rd word are zero.
The 3rd word is zero.
Bit 6
Bit 5
Bit 4
Bit 3
0
0
0
0
0
0
0
0
1
0
1
0
0
1
0
1
0
1
1
1
1
1
1
1
3rd word
4th word, bits 10 ... 15
4th word, bits 0 ... 9
Operation
Bit 2
Bit 1
Bit 0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
0
1
0
0
197