Siemens Sinamics S120 Manual page 666

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

Accessories
11.5 DC link adapter
Risk of fire and damage to equipment due to short-circuit /ground fault
The DC-link connection cables must be laid so that a ground fault or short-circuit is
impossible. A ground fault can cause a fire with smoke development.
• Protect the cables against mechanical damage.
• Use the local installation regulations to avoid this fault.
Also implement one of the following measures:
• Use cables with double insulation.
• Maintain adequate clearance, e.g. by using spacers.
• Lay the cables in separate cable ducts or conduits.
Fire hazard due to overheating when permissible cable lengths are exceeded
Excessively long cable lengths can cause components to overheat with the associated risk
of fire and development of smoke.
• Ensure that the total length of the DC link including the connecting cables does not
NOTICE
Material damage due to loose power connections
Insufficient tightening torques or vibration can result in faulty electrical connections. This
can cause fire damage or malfunctions.
• Tighten all power connections with the specified tightening torques, e.g. line supply
• Check the tightening torques of all power connections at regular intervals and tighten
666
WARNING
WARNING
exceed 10 m.
connection, motor connection, DC-link connections.
them when required. This applies in particular after transport.
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6