Meaning Of Leds - Siemens Sinamics S120 Manual

Booksize power units
Hide thumbs Also See for Sinamics S120:
Table of Contents

Advertisement

8.2.5

Meaning of LEDs

Table 8- 4
Meaning of the LEDs on the Braking Module Booksize
LED
Color
READY
-
Off
Green
Continuous
light
Red
Continuous
light
DC LINK
-
Off
Green
Flashing
light
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Status
The electronics power supply is missing or outside the
permissible tolerance range.
The component is deactivated via terminal.
The component is ready for operation.
Enable missing (input terminal)
Overtemperature
Overcurrent trip
I
t monitoring activated
2
Ground fault/short circuit
Note:
In the event of an overtemperature, the error cannot be
acknowledged until a cooling time has elapsed.
Only braking resistors approved by Siemens for this
component are identified automatically.
The component is not active.
The component is active (DC link is being discharged via
the braking resistor).
Description, cause
DC link components
8.2 Braking Module Booksize
Remedy
Troubleshoot the fault
using the output
terminals and
acknowledge it using
the input terminal.
523

Advertisement

Table of Contents
loading

Table of Contents