Operating Instructions Fire alarm system EBL512 G3, V1.1.x
Disable zone (H2/B1)
When a whole zone is disabled, all alarm points within the zone are
disabled except the addressable manual call points. (This function can
depend on convention / country.)
Disabled zones are listed in menu H4/U1 from which it is also
possible to get a print-out.
Text in display
H2 Disable or re-enable
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
Disable zone: 000
(press ↵)
Disable zone: 001
(press ↵)
Re-enable time: HH:MM
(Default is current time + 3 hours)
Disable zone: 000
(press ↵)
No
Yes
91
Comments
According to chapter
"Access", see page 85.
Press "↲ " to disable.
Press "↲ " to disable
without automatic re-
enablement.
or
Accept the time (+ 3
hours) or set another
time (max + 24 hours),
select "Yes" and press
"↲ " to disable with
automatic re-
enablement.
LED Fault /
Disablements "General
disablements" (L10) will
light up.
Disable another zone or
press "ESC". Scroll to
another menu or press
"ESC".