Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Disable interlocking output (H9/C4)

Interlocking outputs (Type = Interlocking) can be individually
disabled via this menu but not via menu H2/B3.
All interlocking outputs can be collectively disabled via menu H2/B7.
The "Interlocking Combination" (Area / Point) is to be entered to
disable the output. Up to 200 interlocking outputs can be disabled.
Disabled interlocking outputs are listed in menu H4/U1 from which it
is also possible to get a print-out.
The LED Fault / Disablements "General disablements" (L10) is also
indicating one or more disabled interlocking outputs.
Text in display
H9 Interlocking outputs and inputs
C1 Activated interlocking outputs / inputs
C2 Activate interlocking output
C3 Reset interlocking output
C4 Disable interlocking output
C5 Re-enable interlocking output
C4 Disable interlocking output
Disable interlocking output
area: 000 point: 00
(press ↵)
C4 Disable interlocking output
148
Comments
According to chapter
"Access", see page 85.
Write the area number and
"↲ ".
point and press
If more interlocking
outputs shall be disabled
continue the same way.
Press "ESC" to menu C4.
Scroll to another menu or
press "ESC".