Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Re-enable output (H2/B6)

Disabled outputs are listed in menu H4/U1 from which it is possible to
get a print-out.
When all outputs have been re-enabled, The LED
"General disablements" (L10) will be turned OFF, if there are no other
disablements in the system.
Text in display
H2 Disable or re-enable
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
B6 Re-enable output
Re-enable output type:
Re-enable 000001 output 0
000001 output 1
Re-enable control unit: 00 S0
control unit: 00 S1
Re-enable control unit: 00 R0
control unit: 00 R1
Re-enable CU: 00 exp. board 0 output 0
CU: 00 exp. board 0 output 1
Re-enable output type:
3361/3364
S
R
Expansion board
3361/3364
S
R
Expansion board
97
Fault / Disablements
Comments
According to chapter
"Access", see page 85.
Select output type.
S=CU voltage output S0-
S3.
R=CU relay output R0-R1.
Press "
" to accept.
If there are no outputs to
re-enable, menu B6 will be
shown again.
Use "▼" or "▲" to select
the output in the list and
press "↵ ".
Re-enable another output
or press "ESC". Scroll to
another menu or press
"ESC".