Panasonic Electric Works Nordic AB
MEW01349
Rev: -
14
14.1
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
Technical number / Presentation
number
Technical number for COM loop units
The technical number, NNNNNN, is used when programming all
units connected to the COM loops.
Technical number is also used to identify which unit has generated a
fault.
NOTE!
15
Totally 1020
COM loop (technical) addresses can be used for one
control unit, of which up to 512 addresses can be used for alarm
points.
A brand new detector is factory set to COM loop (technical) address
000. Connected on the COM loop, the detector LEDs will start
blinking every second, indicating that an address (001 - 255) has to be
set before the detector will work.
15
Since (technical) address 000 cannot be used, in fact the total number of
addresses will be 4 x 255 = 1020
36
001 - 255
The technical address on the COM
loop.
The addresses don't have to be in
sequence.
The connections on the COM loop
don't have to be in sequence.
The address is for each unit set with
the programming tool 3314