Sensitive fault detection mode (H5/A2)

To increase the possibilities to detect faults during the commissioning,
it is possible to use the "Sensitive fault detection mode". The time
delay for each fault will then be reduced, i.e. you might find some
faults now instead of in the future.
The "Sensitive fault detection mode" turned on is indicated by the
LED Routing equipment "Fault tx activated" (L13) and the "Fault"
output for routing equipment is "activated".
NOTE! Don't forget to turn off this mode after the commissioning.
Text in display
A1 Calibration of supervised outputs
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A2 Sensitive fault detection mode
Sensitive fault detection mode:
A2 Sensitive fault detection mode
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
Off
On
118
Comments
According to chapter
"Access code for service /
maintenance (H5 and
H8)", see page 116.
"↵ "
or
Press
to turn off
s
"↵ "
elect "On" and press
to turn on the sensitive
fault detection mode.
Scroll to another menu or
press "ESC".