MEW01349
Rev: -
Power down (de-energize)
then power up again. ("Cold restart")
Via menu H8/S6 Safe shut down of
control unit. ("Cold restart")
Via RESET button on Main board
and MMI board respectively.
Reset command via WinG3 or
TLON Manager.
Automatically after download of site
specific data (SSD) via a PC &
WinG3. ("Warm restart")
Automatically after download of
S/W and text file via a PC & WinG3.
("Cold restart")
Automatically due to external
44
disturbance.
Operating Instructions Fire alarm system EBL512 G3, V1.1.x
Action
40
and
41
("Cold restart")
NOTE! During the restart, the fault output (relay) for the Fault tx will
be "activated", the supervised 24 V DC outputs S0-S3 will be not
supervised and S0-S3 programmed as normally high will be low for a
few seconds.
During the "restart", no fire alarm can be activated and the following
is show in the display:
Panasonic
40
Both rectifier (mains) and battery disconnected.
41
First press the RESET button on Main board momentarily then the
RESET button on MMI board momentarily.
42
If in the middle of a process, also the SSW might be deleted.
43
The old S/W and text file will be deleted.
44
If this happens, call for service personnel / engineer.
45
Depending on the restart reason, also the SSW might be deleted.
82
Data, etc.
which will be
which will be
deleted
not deleted
SSW
SSD,
FFD, WASV
S/W
FFD, WASV
SSD,
S/W, SSW
FFD, WASV
SSD,
S/W, SSW
FFD, WASV
SSD,
S/W, SSW
FFD, WASV
SSD,
S/W, SSW
FFD, WASV
SSD,
S/W
FFD, WASV
SSD,
S/W, SSW
Data, etc.
Restart
code
00
00 alt. 03
42
42
03
00 alt. 03
43
, SSW
01, 02 alt.
45
04-20