Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Disable zone / address (H2/B2)

Addressable alarm points (also addressable manual call points),
connected to the COM loop, can be individually disabled.
Disabled alarm points, zone / addresses, are listed in menu H4/U1
from which it is also possible to get a print-out.
Regarding disabled analog smoke detector: The sensor values will not
be saved, i.e. only the values saved before and after the disablement
will be used when calculating the week average sensor value.
Disabled alarm points, zone / addresses, have to be re-enabled via
menu H4/B2.
Text in display
H2 Disable or re-enable
B1 Disable zone
B2 Disable zone / address
B3 Disable output
B4 Re-enable zone
B5 Re-enable zone / address
B6 Re-enable output
B7 Disable / re-enable output type
B8 Disable / re-enable alarm devices
B9 Disable / re-enable routing equipment
B10 De-activate alert annunciation function
B2 Disable zone / address
Disable zone: 000 address: 00
(press ↵)
Disable zone: 001 address 01
(press ↵)
Re-enable time: HH:MM
(Default is current time + 3 hours)
No
Yes
92
Comments
According to chapter
"Access", see page 85.
Press "↲ " to disable.
Press "↲ " to disable
without automatic re-
enablement.
or
Accept the time (+ 3
hours) or set another
time (max + 24 hours),
select "Yes" and press
"↲ " to disable with
automatic re-
enablement.