Operating Instructions Fire alarm system EBL512 G3, V1.1.x

Perform monthly test (H1)

The control unit and the installation shall be tested on a regular basis.
If one twelfth of the alarm points are tested each month, the whole
installation will be tested after one year.
In test mode, only the alarm points are tested, i.e. no outputs (no
sounders) will be activated during the test. (Alarm devices can be
tested via menu H8/S5.)
If a real fire alarm is activated, for example by an alarm point not in
test mode, the normal fire alarm functions will be activated, i.e. fire
alarm presentation, outputs (sounders) activated, routing equipment
(fire brigade tx) activated, etc.
See also chapter "The information area priority order", page 22.
NOTE! If the control unit door is left open, the output(s) for routing
equipment (fire brigade tx) might be disabled (if set so in WinG3).
There will be an automatic ending of the test mode one hour after the
latest tested alarm point / zone.
See also chapter "Perform ZONE TEST (Test mode) (H7)", page 127.
Text in display
H1 Perform monthly test
Check that all LEDs light up!
Press 
[ A l l d o t s a r e l i t u p ]
Zones to be set in test mode:
??? ??? ??? ??? Start test: 
87
Comments
According to chapter
"Access", see page 85.
The buzzer (in the C.U.)
sounds and all dots in the
display are shown. All
LEDs light up, incl. LEDs
in units connected via I/O
Matrix board 4582.
If printer 5058 - an
option for control unit
5000 – is mounted
, it
will print out:
ABCDE............Z