Lead-Acid Battery Maintenance - Huawei UPS5000-E-200K-SM User Manual

50 kva power modules
Hide thumbs Also See for UPS5000-E-200K-SM:
Table of Contents

Advertisement

UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)

6.2 Lead-Acid Battery Maintenance

Operating Environment Checklist
No.
Check Item
1
Equipment
room
environment
2
Rodent-proof
measures
3
Installation
position
4
Ambient
temperature
5
Ambient
humidity
Issue 17 (2023-07-10)
Acceptance Criteria
● The fireproof door of
the equipment room
remains closed, and the
air conditioner works
normally without
interruption.
● There is no dust or
flammable sundries in
the equipment room.
Rodent-proof measures
are taken in the
equipment room, such as
rat guard and mouse trap.
There is no air outlet or
refrigerant copper pipe of
the air conditioner placed
above the equipment, and
no other water leakage
risks exist.
Actual temperature: ______
°C (Allowed temperature:
20°C to 30°C;
recommended
temperature: 25°C)
Actual humidity: ______%
RH (5%–95% RH, non-
condensing)
Copyright © Huawei Digital Power Technologies Co., Ltd.
Check Method and
Troubleshooting
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
● Check method:
Measure using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
● Check method:
Measure using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
6 Routine Maintenance
Check
Interval
Monthly
Monthly
Monthly
Monthly
Monthly