UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)
Procedure
Step 1 (Optional) Determine the installation position for the cable entry cabinet, and
draw mounting holes in the installation position based on drawings.
Figure 3-55 Mounting holes for the cable entry cabinet (unit: mm)
Step 2 Remove the right and rear covers from the UPS cabinet, and remove the front and
rear covers from the cable entry cabinet. Put away the removed screws and covers.
Step 3 Adjust the anchor bolts of the cable entry cabinet to make it flush with the UPS
cabinet.
Step 4 Install equipotential plate mounting kits on the same horizontal plane of the UPS
cabinet and cable entry cabinet.
Issue 17 (2023-07-10)
NO TE
This section describes how to install the cable entry cabinet on the right side of the UPS. If
the cable entry cabinet needs to be installed on the left side of the UPS, remove the side
panel of the cable entry cabinet and the cable trough, and install them on the right side of
the cable entry cabinet.