UPS5000-E-(200 kVA-300 kVA)
User Manual (50 kVA Power Modules)

9.6 Bypass Input Electrical Specifications

Item
Input system
Rated input voltage
Rated frequency
Input frequency
Input mode
Overvoltage category

9.7 Battery Specifications

The UPS supports the SmartLi. For details about related parameters, see the
SmartLi user manual.
Item
Battery voltage (lead-acid
battery)
Battery management
Issue 17 (2023-07-10)
NO TICE
Copyright © Huawei Digital Power Technologies Co., Ltd.
Specifications
Three-phase four-wire + PE
380 V AC/400 V AC/415 V AC (line voltage)
50 Hz/60 Hz
±6 Hz (adjustable, 0.5–6 Hz, ±2 Hz by default)
The mains input and bypass input share a power
source or use different power sources.
OVC II
Specifications
● 12 V battery: 30–44 batteries. 34 batteries:
battery inverter output power is derated to
90%; 32 or 30 batteries: battery inverter
output power is derated to 80%.
● 2 V battery: 180–264 batteries. 204–214
batteries: battery inverter output power is
derated to 90%; 180–204 batteries: battery
inverter output power is derated to 80%.
● The number of batteries in the positive battery
string must be the same as that of batteries in
the negative battery string.
NOTE
● The number of batteries is 0 by default and
needs to be set based on site requirements.
Batteries have no neutral wire, and an odd
number of batteries are supported.
● When the UPS works in normal mode, if the
actual load rate exceeds the threshold that could
trigger battery derating, an output overload
alarm is generated.
Intelligent battery management
9 Technical Specifications
228