ABB TZIDC Manual page 30

Digital positioner
Table of Contents

Advertisement

30
TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. G
... Use in potentially explosive atmospheres
... IECEx
Type of protection Ex e – increased safety, Ex n – non-
sparking
Ex marking
IECEx Ex ec
Marking
Ex ec IIC T6 resp. T4...T1 Gc
Type Examination Test
IECEx TUN 04.0015X
Certificate
Type
Increased safety
Standards
IEC 60079-0, IEC 60079-7
IECEx Ex nA
Marking
Ex nA IIC T6 resp. T4...T1 Gc
Type Examination Test
IECEx TUN 04.0015X
Certificate
Type
IP rating 'n'
Standards
IEC 60079-0, IEC 60079-15
Temperature Data
Temperature class
T4 to T1
T6*
*
When using the 'Plug-in module for digital feedback' in temperature
class T6, the maximum permissible ambient temperature range is
−35 to +35 °C.
Special conditions
For the 'Feedback on the actuator position using
proximity switches (Pepperl & Fuchs SJ2-SN)' circuit,
measures outside of the device must be implemented to
prevent an up-scale of the rated voltage by more than
40% in the event of transient disturbances.
Only devices that are suited for operation in hazardous
areas of Zone 2 and the conditions prevailing at the place
of use may be connected to circuits in Zone 2
(manufacturer's declaration or certificate from the test
center).
It is only permissible to connect, disconnect, and switch
live circuits during installation or maintenance, or for the
purpose of carrying out repairs.
Note
It is considered very unlikely that a potentially hazardous
atmosphere would be present in Zone 2 at the same time
that installation or maintenance or repair work was being
carried out.
Only non-flammable gases must be used for pneumatic
power supply.
Only use suited cable entries that meet the requirements
of EN 60079-7 or EN 60079-15.
Electrical Data
In the 'Increased safety Ex ec or non-sparking Ex nA' type of
protection only for connection to a certified intrinsically safe
circuit.
Current circuit (terminal) Electrical information (maximum values)
Signal circuit
(+11 / -12)
Contact input
(+81 / -82)
Switch output
(+83 / -84)
Local communication
interface (LCI)
The following modules may be operated as an option:
Current circuit (terminal) Electrical information (maximum values)
Feedback on the
actuator position using
Ambient temperature Ta
proximity switches,
−35 to +85 °C
(Pepperl & Fuchs SJ2-SN)
−35 to +50 °C*
(Limit1: +51 / −52),
(Limit2: +41 / -42)
Plug-in module for
digital feedback
(+51 / -52)
(+41 / -42)
Plug-in module for
analog feedback
(+31 / -32)
U = 9.7 V DC
I = 4 to 20 mA, max. 21.5 mA
U = 12 to 24 V DC
I = 4 mA
U = 11 V DC
Only for connection to a programming device
using an ABB LCI adapter (Um ≤ 30 V DC)
outside the hazardous area.
U = 8.2 V (Ri approx. 1 kΩ)
U = 5 to 11 V DC
U = 10 to 30 V DC
I = 4 to 20 mA, max. 21.5 mA