Electromagnetic Compatibility - ABB TZIDC Manual

Digital positioner
Table of Contents

Advertisement

TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. G

Electromagnetic compatibility

Requirement
ESD contact discharge
ESD air discharge
Burst 5 kHz
Surge line – line
Surge line – ground
radiated interference immunity
80 MHz to 6 GHz
conducted interference immunity
150 kHz to 80 MHz
supply frequency magnetic fields
*
In the event of line surge load on the plug-in module for analog feedback AO, the analog output signal meets assessment criteria B in accordance with
DIN EN 61000-4-5.
Assessment criteria A:
The device must work as intended during and after the test.
Assessment criteria B:
Impairment in operating performance of the device is permitted during the test. The device must continue to work as intended
after the test.
Component
Chassis
Chassis
Input/output signals
Input/output signals
Input/output signals
Chassis
Input/output signals
Chassis
Standard
Test level
reference
DIN EN 61000-4-2
±4 kV
DIN EN 61000-4-2
±8 kV
DIN EN 61000-4-4
±2 kV
DIN EN 61000-4-5
±1 kV
DIN EN 61000-4-5
±2 kV
DIN EN 61000-4-3
10 V/m
DIN EN 61000-4-6
10 V
DIN EN 61000-4-8
30 A/m
15
Assessment criteria
Required
Complied
B
A
B
A
B
A
B
A*
B
A*
A
A
A
A
A
A

Advertisement