TZIDC DIGITAL POSITIONER | DS/TZIDC-EN REV. G
... Use in potentially explosive atmospheres
... ATEX / UKEX
Type of protection Ex ec – increased safety
Ex marking
Ex marking
Marking
II 3 G Ex ec IIC T6, T4...T1 Gc
Type Examination Test
TÜV 04 ATEX 2702 X
Certificate
Certificate (UKEX)
EMA22UKEX0032X
Type
Equipment for increased safety
Device class
II 3 G
Standards
EN 60079-0, EN 60079-7
Special conditions
For the 'Feedback on the actuator position using
proximity switches (Pepperl & Fuchs SJ2-SN)' circuit,
measures outside of the device must be implemented to
prevent an up-scale of the rated voltage by more than
40% in the event of transient disturbances.
It is only permissible to connect, disconnect, and switch
live circuits during installation or maintenance, or for the
purpose of carrying out repairs.
Note
It is considered very unlikely that a potentially hazardous
atmosphere would be present in Zone 2 at the same time
that installation or maintenance or repair work was being
carried out.
Only non-flammable gases must be used for pneumatic
power supply.
Only use suited cable entries that meet the requirements
of EN 60079-7.
In the case of TZIDC, the following shall apply for safe use in
the Ex 'ec IIC' type of protection:
Only devices that are suited for operation in
hazardous areas of Zone 2 and the conditions
prevailing at the place of use may be connected to
circuits in Zone 2 (manufacturer's declaration or
certificate from the test center).
Temperature Data
Device group II 3 G
Temperature class
T4 to T1
T6*
*
When using the 'Plug-in module for digital feedback' in temperature
class T6, the maximum permissible ambient temperature range is
−35 to +35 °C.
Electrical Data
In 'Increased safety Ex ec' type of protection only for
connection to a certified circuit for increased safety.
Current circuit (terminal) Electrical information (maximum values)
Signal circuit
U = 9.7 V DC
(+11 / -12)
I = 4 to 20 mA, max. 21.5 mA
Contact input
U = 12 to 24 V DC
(+81 / -82)
I = 4 mA
Switch output
U = 11 V DC
(+83 / -84)
Feedback on the
U= 8,2 V (Ri approx. 1 kΩ)
actuator position using
proximity switches,
(Pepperl & Fuchs SJ2-SN)
(Limit1: +51 / −52),
(Limit2: +41 / -42)
Plug-in module for
U = 5 to 11 V DC
digital feedback
(+51 / -52)
(+41 / -42)
Plug-in module for
U = 10 to 30 V DC
analog feedback
I = 4 to 20 mA, max. 21.5 mA
(+31 / -32)
Local communication
Only for connection to a programming device
interface (LCI)
using an ABB LCI adapter (Um ≤ 30 V DC)
outside the hazardous area.
Ambient temperature Ta
−35 to +85 °C
−35 to +50 °C*