General - ABB i-bus BDB/S 1.1 Product Manual

Eib / knx data logging unit
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
3.3.3

General

© 2006 ABB STOTZ-KONTAKT GmbH
Commissioning
Fig. 11:
Communication objects General 245...247
No.
Function
245
Recall all switch positions
A recall of all switch positions of the monitored channels is started.
Telegram value "1" = recall
Telegram value "0" = do not recall
246
Send all operating data
Send the current operating data via the communication objects
"Channel X switching operations – Number",
"Channel X operating hours – Number",
"Channel X switching operations – Alarm" and
"Channel X operating hours – Alarm"
Telegram value "1" = send
Telegram value "0" = do not send
247
Enable delete/overwrite
If a "1" is received the enable to delete/overwrite of the operating data is issued and a time
window of 10 seconds is activated. The time window closes automatically 10 seconds after
the last change and the communications object value is reset to "0" and sent on the bus.
Via the communications object "Delete all operating data - System" all operating data can be
deleted in the Data Logging Unit.
When counting upwards the counter value is set to zero.
When counting downwards the counter value is set to start value.
The operating hours counter, start and limit values, the switching operations counter, start
and limit values can be modified via the respective communication objects via the bus.
Telegram value "1" = time window active
Telegram value "0" = time window not active
Table 6:
Communication objects General 245...247
Object name
Data type
System
EIS 1, 1-Bit
DTP 1.001
System
EIS 1, 1-Bit
DTP 1.001
System
EIS1, 1 Bit
DTP 1.001
Flags
C, W
C, W
C, W
32

Advertisement

Table of Contents
loading

Table of Contents