Device Technology; Technical Data - ABB i-bus BDB/S 1.1 Product Manual

Eib / knx data logging unit
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
2

Device technology

Fig. 1:
BDB/S 1.1
2.1

Technical data

Power supply
Connections
Operating and display elements
Enclosure
Safety class
Isolation category
EIB / KNX safety extra low voltage
Temperature range
Ambient conditions
Design
Installation
Mounting position
Weight
Housing/colour
Approvals
CE mark
© 2006 ABB STOTZ-KONTAKT GmbH
Device technology
For installation in the distribution board. The device is used for recording of
switching operations and operating hours on 35 channels. The BDB/S 1.1 is
operational after of the bus voltage. The module is programmed directly via
the application program ETS. The connection to the ABB i-bus
established via the bus connection terminal at the front of the device.
- Bus voltage
- Current consumption, bus
- Leakage loss, bus
- EIB / KNX
- Programming LED
- Programming button
- IP 20
- II
Overvoltage category
Pollution degree
SELV 24 V DC
- Operation
- Storage
- Transport
- Maximum air humidity
- Modular installation device (MDRC)
- Dimensions
- Mounting width in space units
- Mounting depth
- On 35 mm mounting rail
- as required
– 0.1 kg
- Plastic housing, grey
- EIB / KNX to EN 50 090-1, -2
- in accordance with the EMC guideline and
-
low voltage guideline
Table 1:
Technical data
®
21 ... 32V DC
< 12 mA
Max. 250 mW
via bus connection terminals
for assignment of the physical address
for assignment of the physical address
to DIN EN 60 529
to DIN EN 61 140
III to DIN EN 60 664-1
2 to DIN EN 60 664-1
-5° C...+ 45° C
-25°C...+ 55°C
-25°C...+ 70°C
93%, no condensation allowed
Modular installation device, ProM
90 x 36 x 64.5 mm (H x W x D)
2 (2 modules at 18 mm)
64.5 mm
to DIN EN 60 715
Certification
is
6

Advertisement

Table of Contents
loading

Table of Contents