ABB i-bus BDB/S 1.1 Product Manual page 25

Eib / knx data logging unit
Table of Contents

Advertisement

®
ABB i-bus
EIB / KNX
© 2006 ABB STOTZ-KONTAKT GmbH
Commissioning
Switching operations count method
Options:
Total value/Remaining value
Option Total value = counting upwards beginning at 0.
Option Remaining value = counting downwards beginning at the start value
Note:
A 1 = 1 switching operation.
If the option Total value is selected, the following two parameters are
displayed.
Switching operations limit value
Options:
0...1000...4.294.967.295
The limit value for the switching operations is set with this parameter. If this
value is reached the communication object "Channel 1 switching operations
- Alarm" sends a "1".
Note:
Thereafter counting will continue up to the end value of
4.294.967.295. The counter value stops at 4.294.967.295.
Overwrite switching operations limit value with download
Options:
no/yes
Option no = switching operations limit value is not overwritten
Option yes = switching operations limit value is overwritten
Note:
Changes of the limit value via the bus with a download is not
taken into consideration. The parameterised value is set as a
limit value.
25