Commissioning
Fig. 12:
General communication objects 248 and 249
No.
Function
248
Delete all operating data
Deleting of the operating data switching operations and operating hours. Deleting applies for
all channels.
If a "1" is received the values of the communication objects
"Channel X switching operations – Number" and
"Channel X operating hours – Number"
are set to zero counting up and set to the start value when counting down.
Before the operating data is deleted a "1" must be received on the communications object
"Enable delete/overwrite - System".
Telegram value "1" = delete
Telegram value "0" = do not delete
249
In operation
This communication object is only active if "yes" has been selected for the parameter Send
cyclic "In operation" telegram. As long as the communication object is activated it sends an
In operation telegram.
Telegram value
Table 7:
General communication objects 248 and 249
Object name
System
System
"1" system in operation
Data type
Flags
EIS 1, 1-Bit
C, W
DTP 1.001
EIS1, 1 Bit
C, R, T
DTP 1.003