29.4

Test of Alarm Devices (H8/S4)

The programmable outputs of type "Alarm device" can be collectively activated via this
menu (H8/S4), which allows for the alarm devices to be tested. This procedure includes
Addressable sounder base 3379, wireless detector 4611, all visual alarm devices 4480,
4481, 4482, 4487 and OWS.
The test cannot be started if a fire alarm in the system is already active.
One or all Control Units can be selected. When the test starts, the alarm devices will sound
continuously (steady) for approx. 5 seconds, be silent for approx. 25 seconds, sound for
approx. 5 seconds and so on
Note: Disabled and silenced alarm devices will also be tested and will sound during the
test.
The test will continue for one hour if not terminated via this menu (H8/S4) or if a fire alarm
is activated in the system. After one hour, when the test mode is terminated, a message is
shown in the General event log (menu H4/U7).
Action
"Menu"
Scroll to menu H8.
"↲"
Scroll to menu S4.
"↲"
"↲"
"↲"
"↲"
The OWS can be tested by testing the alarm output that triggers the OWS.
45
For the alarm devices 3379, 4461, 4482 and 4487, the tone with the highest priority level (and type "alarm
device") will be automatically selected.
.
45
Text in display
H8 Maintenance
S1 Dis- / Re-connect loop / zone line input
S2 Acknowledge SERVICE signal
S3 Clear weekly average
S4 Test of alarm devices
S5 Safe shut down of control unit
S6 Activate address in alarm mode
S7 Synchronize the control units
S8 Activate / Reset outputs
S4 Test of alarm devices
Press ↵ to start test.
Test of alarm devices control unit: 00
in progress. Press ↵ to end test
Test of alarm devices, control unit 00
Press ↵ to return to menu
Test of alarm devices ended.
S4 Test alarm devices
All
155
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Write control unit
number or press "►" for
"All".
Press "↲" to start the
test.
The test will continue for
one hour if not stopped
via this menu (S4) or if a
fire alarm is activated in
the system.
Press "↲" to terminate
the test.
Scroll to another menu
or press "ESC".