User Level 2A - Panasonic Brooks FireTracker FT1020G3 Operation Manual

Hide thumbs Also See for Brooks FireTracker FT1020G3:
Table of Contents

Advertisement

Push button
P1
P2
P3
P4
P9
OWS
AS1668 Fan / Damper Control
Zone Disablement
19" Rack Display/control
modules
6.3.4

User level 2A

After the door has been opened with 003 key ("Door open" symbol
you have access to level 1 and after log on as "Information only" (level 2A), the following
menus are accessible:
H4 Present system status
U1 Disablement
U2 Disablement by time channel
U3 Open doors
U4 Sensor values
U5 Sensors activating SERVICE signal
U6 Technical warning
U7 Event log
U8 Information
H6 FAULT Acknowledge, Note: Information only
H9 Interlocking outputs and inputs
C1 Activated interlocking outputs / inputs
H10 Change password (In this case for "Information only")
Pressing "RESET" or "DISABLE" button MUST be preceded with pressing "SILENCE ALARM".
20
Operation/function
Silence buzzer in FT1020G3
Silence all alarm devices (OWS or sounders).
Reset fire alarms
20
Disable active alarm
20
Scroll / browse through the active queued alarms
OWS controls, if fitted
Manual override of AS1668 fan or Damper controls, if fitted
Quick access to zone disable / re-enable, if fitted
Access to 19" rack control buttons
44
Operation Manual
FT1020G3 Rev 2.10.4