Table 14 Damper indicators and controls

LED indicator & buttons
FIRE MODE General fire mode - Red
FIRE
Damper open - Red
NON- FIRE Damper close - Green
Fault
Fan fault - Yellow
POWER
Power fault - Yellow
FLT
LED – Red
FIRE
Button
LED – Green
AUTO
Button
LED - Yellow
NON FIRE
Button
5.5

Generic FT1020G3 Display and Control Modules

Each 19" rack mount display / control module comprises 3 parts: PCB, plastic spacer and
decal label. The PCB for all display modules is only one PCB but fitted with switches and
LEDs to suit different applications. All switches and LEDs are fully programmable in
EBLWin as an input (switch) or as an output (LED).
Each display module can be manually addressed with the address setting tool set to
Advanced Mode. All Display Panel modules must be configured with software ≥ V2.4.x. to
be recognised by the FDCIE.
The generic and display modules are mounted on the ancillary 19" metal rack, up to 8
modules can be connected on an ancillary rack. Each module required to be connected to
the monitor card 1204 via a ribbon cable to communicate with the loop and to provide 24V
/ 5V supply. The ribbon cable is equipped with 10 way socket to plug in the IDC header in
each module.
All LEDs in every module can be configured via DIP switch on each module to provide 3
colours; red, green and amber. Even within the same module, different colour indicators
can be configured.
Notes:
1205, 1206 & 1211: Only addresses 0-5 can be assigned. I/O matrix type selection is not
required, permanently selected for each type.
1207 & 1208: Require 2 consecutive COM loop addresses per module and will
automatically take on the next address.
The four 50mm different display and control modules are shown in Figure 16 below. The
functionality and requirements are described in section 5.5.1 to 5.5.4 below.
Indicating
Illuminates to indicate general fire.
Illuminates to damper is opened.
Illuminates normal status i.e. damper closed.
Illuminates when the signal to change the damper status
is restored, either via manual override switch or by the
FDCIE in Auto mode but the feedback signal confirming
the change of damper state has not been received by
4461 input connected the damper field control (if used).
Or
There is an open circuit in the 4461 supervised input
where the feedback from the field damper control is
connected.
Or
The damper device suppling damper condition is faulty
Illuminates in case of no power controlling the damper
Indicates manual control when the "On" button is pressed
Manual override control to open the damper manually
irrespective of any alarm condition in the FDCIE.
Indicates "Auto" position of the button, normal operation
Pressed to put the damper in "Auto" mode i.e. the
damper
may open or close automatically depending on the
alarm condition in the FDCIE
Indicates "Off" position of the button, damper close
manually
Manual override control to close the damper if it was
opened
irrespective of any alarm condition in FDCIE.
37
Operation Manual
FT1020G3 Rev 2.10.4