26.4

Display Current Consumption in Unit (H5/A4)

26.4.1

Power Supply (Control Unit)

Voltage: The 24V measured by the CPU on the main board. Corresponds to the output
voltage at the power supply outputs on connector J3.
Earth voltage: Measured from 0V (connector J4:2) to earth.
Current from power supply: The total current consumption (including the charging current
at 24V) for the selected control unit (FDCIE) when it is connected to the mains (230 VAC),
i.e. this function is not working by battery backup.
26.4.2

Battery

Voltage: The battery voltage at connector J4:4-5.
Charging current: The battery charging current for the selected control unit (FDCIE).
Temperature: The temperature detected by the battery temperature sensor.
Resistance in battery circuit: During the battery capacity check the resistance in the
battery circuit is measured. A resistance > 0.5 Ω will result in a "Low battery capacity" fault.
Checked every 4th hour.
Action
Text in display
"Menu"
Scroll to menu H5.
H5 Service
A1 Calibration of supervised output
"↲"
A2 Sensitive fault detection mode
A3 Service mode for COM-loop
A4 Display current consumption in Control Unit
A5 Display current consumption on COM-loop
A6 Display statistics for communication
A7 Activate address setting mode for DU
A8 Setup wireless detectors
A9 SSD information
Select control unit: : 00 (press ↵)
Scroll to menu A4.
A4 Display current consumption in control unit
"↲"
"↲"
Please wait......
No reply from control unit.....
Power supply (Control Unit 00)
Voltage: xx.xx V
Earth voltage: xx.xx V
Current from power supply: xxx mA
Battery
Voltage: xx.xx V
Charging current: x mA
Temperature xx°C
Resistance in battery circuit: xxxxx mΩ
A4 Display current consumption in unit
"↲" or "ESC"
Note: If you get "No reply from control unit....." the control unit doesn't exist or doesn't
answer
139
Operation Manual
FT1020G3 Rev 2.10.4
Comments
According to chapter
"Access", see page 42.
Write control unit
number and press "↲".
If the control unit is not
exist or not responding.
Information is
automatically updated
every 5 second.
Scroll to another menu
or press "ESC".