Chapter 14. Diagnostics

14.4.4 Energy Pack Diagnostics (Error Code 18-1, Low Battery Fault)

The Controller provides two status bits, %S0014 and %SA0011, which can be monitored by
user logic to determine the Energy Pack's operating condition.
282
%S0014
%SA0011
0
0
1
1
1
0
PACSystems* RXi Distributed IO Controller User Manual
Energy Pack Status
Energy Pack is connected and operational.
Energy Pack is in one of the following states; the fault
table has not been cleared:
Charging. (The RXi Controller's %S0014 and
%SA0011 battery status bits remain set during the
Energy Pack's charging cycle.)
Not connected or failed.
The CapPack is nearing its end-of-life and should be
replaced.
The Energy Pack is not connected or failed, or the
CapPack is nearing its end-of-life; the Controller fault
table has been cleared.
The %SA0011 bit remains set until the Controller fault
table is cleared.
The %S0014 bit continues to indicate the Energy
Pack's current status after the Controller fault table is
cleared.
GFK-2816F