7 FUNCTION

7.15 GX Developer system monitor

(a)
(b)
7 - 37
It is possible to confirm the following information for Basic model QCPUs connected to
personal computers with the GX Developer system monitor (see illustration below.)
• Installed status
• Operation status
• Module's detailed information
• Product information
(a)
Installed status
You can confirm the types and points of the modules loaded on the
selected base unit.
"Not installed" will be displayed for slots in which modules have not been
mounted.
When slots have been set as "Empty" with the PLC parameter's I/O
allocation setting, the module's model will not be displayed when if a
module has been mounted.
(b)
Operation status
Enables the I/O number, the module type and the number of modules
mounted for each of the slots on the selected base unit to be confirmed.
If the operation status shows 0 empty points and an allocation error is
displayed, it means that the PC parameter's I/O allocation and the actual
status are different.
In this event, align the PLC parameter's I/O allocation with the actual status
by allocating an I/O.
(c)
Base
Enables the status of the modules mounted onto the base unit in use to be
confirmed.
The module column displays an error or warning status if even one module
is faulty.
(d)
Diagnostics
This function is used to confirm the status of Basic model QCPU and errors.
MELSEC-Q
(c)
(d)
(e)
(f)
(g)
7 - 37