6.20 System Display of CPU Module with GX Developer

When the CPU module is connected to GX Developer, this function can check the following items of the modules on
the base unit in the System Monitor screen.
• Installed status
• Parameter status
• Module's Detailed Information
• Product information
(1)
(2)
(1) Installed status
The control CPU, model name, and the number of points of the modules on the selected base unit can be
checked.
"Unmounting" is displayed in the field of a number of slot where a module is not mounted.
The model name of a module on a slot to which "Empty" is set in the I/O assignment tab of the PLC parameter
dialog box is not displayed.
When using a redundant base unit, mounted status of the power supply module is also displayed.
(2) Parameter status
The I/O number, type, and the number of points of the module on each slot of the selected base unit can be
displayed.
If the Parameter status displays "0" for an empty slot or assignment error, it indicates that the I/O assignment
setting of the PLC parameter dialog box and the mounted status differs. Therefore, change the I/O assignment
setting so that it may match with the mounted status.
When using a redundant base unit, mounted status of the power supply module is also displayed.
注 1
Note6.10
Universal
Before monitoring the Q02UCPU, Q03UDCPU, Q04UDHCPU, Q06UDHCPU, Q13UDHCPU, or Q26UDHCPU, check
the versions of the CPU module and GX Developer.(
Figure 6.84 System Monitor screen
Appendix 2)