ABB GOE 2600 Installation And Commissioning Manual page 57

Transformer bushing
Table of Contents

Advertisement

4.
Connect the measuring equipment.
1.
Connect the low voltage cable to the
stud (57).
2.
Connect the high voltage cable to the
outer terminal.
3.
Connect the ground cable to the bushing
flange (65).
5.
Measure the capacitance (C
Record the capacitance (C
6.
Measure the capacitance (C
Record the capacitance (C
7.
Install the cover (58).
8.
Connect the outer terminal of the bushing to the external connections.
End of instruction
Installation and commissioning guide
1ZSC000563-AAF EN, REV. 4, 2021-06-23
) between the outer terminal and the stud (57).
1
) for future reference.
1
NOTE!
Refer to the table for the nominal capacitance (C
) between the stud (57) and the flange (65).
2
) for future reference.
2
CAUTION!
The test tap is not self-grounding!
The bushing can be destroyed if the test tap is not grounded. Because the capacitance (C
is usually relatively small, the test tap must never be open-circuited when applying a
voltage to the bushing. It must always be grounded or connected to an external impedance.
CAUTION!
Do not energize the bushing without the cover or a test adapter installed. The cover
connects the outermost conductive foil to ground and will prevent damage to the bushing.
CAUTION!
Make sure that the cover is correctly installed with the O-ring in place, when the bushing is
not in use. The purpose is to prevent dust and water from entering the tap.
), Nominal capacitance, page 55.
1
)
2
57