Installation Manual – BTS3606A Cabinet Installation
Airbridge BTS3606&3606A CDMA Base Station
Figure 5-43 AC power lightning arrester used in the case of two-phase power supply
To connect the 110 V two-phase power cable, simply connect the L1, L2 and N lines to
the corresponding L1, L2, and N terminals on the lightning arrester. The installation
procedure and principles are the same as those in the case of three-phase power
supply. For details, see section 5.7.3 I. "Installing Three-Phase Power Cable".
cable-L1
cable-L1
cable-L2
cable-L2
Figure 5-44 Connecting the 110 V power cables
Huawei Technologies Proprietary
5-42
Chapter 5 Installing Cables