Mitsubishi Electric A800 Instruction Manual page 65

Hide thumbs Also See for A800:
Table of Contents

Advertisement


The operating capacity of the relay outputs (terminal symbols A1, B1, C1, A2, B2 and C2) should be 30 VDC, 0.3 A. (Relay output has basic isolation from the inverter
internal circuit.)

Control circuit terminals on

Environment (For the detail, refer to
LD, ND (initial setting), HD: -10 to +50°C (14 to 122°F)
Surrounding air temperature
SLD: -10 to +40°C (14 to 104°F)
Ambient humidity
95% RH or less
Maximum altitude
2500m (8202 feet)
 Wiring protection
Class T, Class J, Class CC, or Class L fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
For the FR-A820 series, Class T, Class J, or Class CC fuse, or UL 489 Molded Case Circuit Breaker (MCCB) must be provided.
FR-A820-[]
Rated fuse voltage (V)
Without power
factor improving
Fuse maximum
reactor
allowable rating
(A)

With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-A820-[]
Rated fuse voltage (V)
Without power
factor improving
Fuse maximum
reactor
allowable rating
(A)

With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-A840-[]
Rated fuse voltage (V)
Without power
factor improving
Fuse maximum
reactor
allowable rating
(A)

With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)

FR-A840-[]
Rated fuse voltage (V)
Without power
factor improving
Fuse maximum
reactor
allowable rating
(A)

With power factor
improving reactor
Molded case circuit breaker (MCCB)
Maximum allowable rating (A)


Maximum allowable rating by US National Electrical Code. Exact size must be chosen for each installation.
 Short circuit ratings
• 200 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 264 V Maximum.
• 400 V class
Suitable For Use in A Circuit Capable of Delivering Not More Than 100 kA rms Symmetrical Amperes, 550 V or 600 V Maximum.
28
page 5
are safely isolated from the main circuit.
page
3.)
During operation
00046
00077
00105
00167
(0.4K)
(0.75K)
(1.5K)
(2.2K)
240 V or more
15
20
30
40
15
20
20
30
15
15
25
40
00930
01250
01540
01870
(18.5K)
(22K)
(30K)
(37K)
240 V or more
225
300
350
400
200
250
300
350
225
300
350
450
00023
00038
00052
00083
(0.4K)
(0.75K)
(1.5K)
(2.2K)
500 V or more
6
10
15
20
6
10
10
15
15
15
15
20
00930
01160
01800
02160
(37K)
(45K)
(55K)
(75K)
500 V or more
200
250
300
175
200
250
300
225
250
450
450
In storage
-20 to +65°C (-4 to +149°F)
95% RH or less
2500m (8202 feet)
00250
00340
00490
00630
(3.7K)
(5.5K)
(7.5K)
(11K)
60
80
150
175
50
70
125
150
60
80
110
150
02330
03160
03800
04750
(45K)
(55K)
(75K)
(90K)
500
500
400
500
600
700
500
700
900
1000
00126
00170
00250
00310
(3.7K)
(5.5K)
(7.5K)
(11K)
30
40
70
80
25
35
60
70
30
40
60
70
02600
03250
03610
04320
(90K)
(110K)
(132K)
(160K)
350
400
500
600
500
During transportation
-20 to +65°C (-4 to +149°F)
95% RH or less
10000m (32808 feet)
00770
(15K)
200
200
190
00380
00470
00620
00770
(15K)
(18.5K)
(22K)
(30K)
90
110
150
175
90
100
125
150
90
100
150
175
04810
05470
06100
06830
(185K)
(220K)
(250K)
(280K)
700
800
900
1000