INVERTER INSTALLATION AND PRECAUTIONS

 Inverter model
FR -
A8 0
2
-
Symbol Voltage class
Symbol
00023 to 06830
2
200 V class
400 V class
0.4 to 280K
4

Specification differs by the type. Major differences are shown in the table below.
Type
FM
Terminal FM: pulse train output
Terminal AM: analog voltage output (0 to 10 VDC)
(terminal FM equipped model)
CA
Terminal CA: analog current output (0 to 20 mADC)
Terminal AM: analog voltage output (0 to 10 VDC)
(terminal CA equipped model)

Applicable for the FR-A820-00340(5.5K) or higher, and the FR-A840-00170(5.5K) or higher.
Capacity plate
Inverter model
Serial number
NOTE
• In this Instruction Manual, the inverter model name consists of the applicable motor capacity and the rated current. (Example) FR-A820-00046(0.4K)
 Inverter placement
Installation on the enclosure
Fix six positions for the FR-A840-04320(160K) or higher.
 Installation environment
Before installation, confirm that the following environment conditions are met.
Item
LD, ND (initial setting), HD
Surrounding air
temperature

SLD
Ambient humidity
Storage temperature
Atmosphere
Altitude
Vibration

Temperature applicable for a short time, e.g. in transit.

For the installation at an altitude above 1,000 m (3280.80 feet) up to 2,500 m (8202 feet), derate the rated current 3% per 500 m (1640.40 feet).
2

2.9 m/s
or less for the FR-A840-04320(160K) or higher.

Surrounding Air Temperature is a temperature measured at a measurement position in an enclosure.
Ambient Temperature is a temperature outside an enclosure.

For the amount of heat generated by the inverter unit, refer to the Technical News (MF-Z-116) contained in the enclosed CD-ROM.
00046
-1
Description
Symbol Type∗1
Inverter SLD rated current (A)
-1
Inverter ND rated capacity (kW)
-2
Monitor output
Rating plate
• Install the inverter on a strong surface securely with screws.
• Leave enough clearances and take cooling measures.
• Avoid places where the inverter is subjected to direct sunlight, high temperature and high humidity.
• Install the inverter on a nonflammable wall surface.
• When encasing multiple inverters, install them in parallel as a cooling measure.
Vertical
Allow clearance.

For the FR-A820-00250(3.7K) or lower and FR-A840-00126(3.7K) or lower, allow 1 cm (0.39 inches) or more clearance.

When using the FR-A820-01250(22K) or lower and FR-A840-00620(22K) or lower at the surrounding air temperature of
40°C (104°F) or less (30°C (86°F) or less for the SLD rated inverter), side-by-side installation (0 cm clearance) is available.

For replacing the cooling fan of the FR-A840-04320(160K) or higher, 30 cm of space is necessary in front of the inverter.
Refer to
the Instruction Manual (Detailed) for fan replacement.
-10 to +50°C (non-freezing)
-10 to +40°C (non-freezing)
With circuit board coating (conforming to IEC60721-3-3 3C2/3S2): 95% RH or less (non-
condensing),
Without circuit board coating: 90% RH or less (non-condensing)
-20 to +65°C

Indoors (free from corrosive gas, flammable gas, oil mist, dust and dirt)
Maximum 2,500 m above sea level.

2
5.9 m/s
or less at 10 to 55 Hz (directions of X, Y, Z axes)

Circuit board coating
Symbol
(conforming to IEC60721-3-3 3C2/3S2)
FM
CA
Without
Without
-60
With
-06∗2
With
Initial setting
Built-in
Control logic
EMC filter
frequency
OFF
Sink logic
60 Hz
ON
Source logic
50 Hz
Inverter model
Input rating
Output rating
Serial number
Clearances (front)
FR-A820-03160(55K) or lower,
FR-A820-03800(75K) or higher,
FR-A840-01800(55K) or lower
FR-A840-02160(75K) or higher
10cm
(3.94inches)
or more
5cm
5cm
10cm
(1.97inches)
(1.97inches)
(3.94inches)
or more∗1,∗2
or more∗1,∗2
or more
10cm
(3.94inches)
or more
Description
INVERTER INSTALLATION AND PRECAUTIONS
Plated conductor
Without
Without
With
Rated
Pr.19 Base frequency voltage
9999
(same as the power supply voltage)
8888
(95% of the power supply voltage)
Production year
and month
Clearances (side)
20cm
(7.87inches)
5cm
or more
(1.97
10cm
inches)
(3.94inches)
or more
∗1,∗3
or more
Inverter
20cm
(7.87inches)
or more
Enclosure
Measurement
position
Inverter
5 cm
5 cm
(1.97 inches)
(1.97 inches)
5 cm
Measurement
(1.97 inches)
position
3