8.3 Outline of Lossnay operation
(1)
Start of operation
Start of daily operation
End of daily operation
(2)
Inspection after usage
(3)
Bypass operation month
(4)
Total operation time
8.4 Characteristics in change of Lossnay Core over time
Two Lossnay Cores were removed from the 18 Lossnay LS-200
installed in the Meiji Seimei Building, and the static pressure loss
and exchange efficiencies were measured. The comparison with
the initial value is shown on the right. The appropriate air volume
for one Lossnay Core is 500 m
3
was ±200 m
/hr of this value.
8.5 Conclusion
(1) Changes in the characteristics of the Lossnay Core after approximately eleven years of use and an estimated 28,000
operation hours were not found.
In numerical values, the static pressure loss was 150 to 160 Pa at 500 m
exchange efficiencies had decreased slightly at above 500 m
remained in the measurement error range.
(2) Looking at the appearance, the Core surface was black with dust, but there were no gaps, deformation or mold that would
pose problems during practical use.
CHAPTER 3
: September 1972
: 7:00
Average daily operation 11 hours
: 18:00
: November 1983
: Three months of April, May, June
: (134 – 33) months × 25 days/month × 11 hours/day = 27,775 hours
3
/hr, and the measurement point
General Technical Considerations
Characteristics in change of Lossnay Core over time
90
80
Enthalpy recovery
efficiency during heating
70
300
200
100
0
300
Treated air volume (m
3
/hr which was a 10 Pa increase, and the
3
/hr. However, this is considered to be insignificant and
Data from delivery (1974)
Data from 1983
Heat recovery
efficiency
Static pressure Loss
500
700
3
/h)
35