Mitsubishi Electric Lossnay LGH-100RX3-CAN Technical Manual page 114

Hide thumbs Also See for Lossnay LGH-100RX3-CAN:
Table of Contents

Advertisement

2 remote controller system with multiple Lossnay units
Remote controller
PZ-41SLB-E
It is also possible to operate 2 remote controller units when using multi-
ple Lossnay units.
Interlocking multiple units
When the operation signal is a uncharged a-contact signal
Lossnay
A/C
Power suupy
Power suupy
Air conditioning
Air conditioning
Remote
unit side remote
unit side remote
controller
controller
controller
PZ-41SLB-E
Interlocking is possible from multiple air conditioning units, etc.
(excluding pulse input)
(Separately sold parts are necessary depending on the operation signal).
Interlocking/individual joint systems
By making the group setting, interlock settings have become possible.
(Joint use of the air conditioner remote controller and Lossnay remote
controller is possible.)
Operation settings
Centralised
Indoor unit
controller
(01)
Outdoor
(201)
unit (51)
MA remote
controller
Applicable indoor units are C type or later (for use with MA remote con-
troller) models
Do not set the air conditioning unit and Lossnay unit to be part of the
same group.
Power supply
Power supply
A/C
A/C
Power suupy
Power suupy
Air conditioning
unit side remote
controller
Lossnay (02)
Lossnay M-NET
remote controller
(PZ-52SF-E)(102)
Group 1
Group 2
( ) address
Use Lossnay remote controller PZ-41SLB-E .
(Do not use PZ-52SF-E).
Lossnay transmission connection terminal
LGH-50 and 100RX types
1
2
Remote Controller Input Terminal
Transmission cable
Setting
Transmission
cable
Use Lossnay M-NET remote controller PZ-52SF-E .
(Do not use PZ-41SLB-E).
Lossnay transmission connection terminal
M-NET Transmission cable
input terminal block
LGH-50 and 100RX types
A B S
Round terminal
M-NET
Transmission cable
Setting
LGH-50 and 100RX types
SA1
SA1
0
When the address number has been changed, the data in the memory is
automatically reset.
LGH-200RX type
3
4
5
6
5
6
A
B
S
Main/Sub switch (SW1)
Main
Sub
(Set to Main when
shipped from the factory)
LGH-200RX type
TB5
TB5
5
6
A
B S
Shielded wire
LGH-200RX type
Upper
circuit
board
[Sub]
ex. SA1 = 0,
SA2 = 2
Lower
circuit
board
[Main]
ex. SA1 = 0,
SA2 = 1