Mitsubishi Electric Lossnay LGH-100RX3-CAN Technical Manual page 119

Hide thumbs Also See for Lossnay LGH-100RX3-CAN:
Table of Contents

Advertisement

Combined Line Method
Connect the transmission cable from the first Lossnay to the second, the second to the third, and so on up to a maximum of 15
units.
(1) Up to four wires can be connected to one signal terminal when a transmission cable is ø0.65 or strand wire 0.3 mm
to 2 wires in other cases.
(2) The signal is non-polar, so it is not necessary to align polarity.
Lossnay Main/Sub Setting
Be sure to make the Main/Sub setting when operating multiple Lossnay units.
When operating multiple Lossnay units, set the first one to "Main," set the second and following to "Sub."
Be sure the power is off when making the settings.
Change the Main/Sub switch (SW1) on the control board to "Sub" for the second and following Lossnay units.
Operation Method
Up to 15 Lossnay units (up to seven units when using LGH-200RX type) can be operated when running at the same time.
(Individual control is not possible)
Note:
In the case of LGH-200RX type, there are two circuit boards installed in each unit. Therefore, count each unit as two units in
calculations when controlling multiple units. For example, 5 LGH-200RX type units would count as 10 units. (For 200RX type
only, a maximum of seven units is possible.)
116
Transmission
cable
Lossnay
Power supply
Remote
controller
PZ-41SLB-E
Transmission
cable
(Main)
Lossnay
Power supply
Remote controller
PZ-41SLB-E
Connect to
5
6
remote controller
(PZ-41SLB-E)
5
6
Connect to third
Lossnay
Lossnay
Lossnay
Power supply
Power supply
Set to Main
Set to Sub
Main/Sub selection switch
(SW1)
Main Sub
(Sub)
(Sub)
Lossnay
Lossnay
Power supply
Power supply
2