5. Examples of Applications Using Exter-
nal Control Input Terminals, Operation
Monitor Output Terminals and Malfunc-
tion Monitor Output Terminals
Various applications are possible by using the input/output termi-
nals as shown below.
Input/Output Specifications
Terminal
1
External control input ter-
minal block
( TM2 1 2 3 )
2
Operation monitor output
terminal block
( TM3 9 0 )
3
Malfunction monitor out-
put terminal block
( TM3 7 8 )
Lossnay Main/Sub Setting
For a multiple Lossnay system that will begin operation from one signal from an air conditioner or the like, make sure the unit
connected to the signal cable from the air conditioner is set to "Main," and all the others are set to "Sub."
This is the input terminal block for start/stop the Lossnay unit using external
equipment, such as a Mr. Slim ( A-control ) indoor unit or the BMS ( Building
Management System ) .
Signal input can be by voltage ( 12V-24V DC ) or uncharged a-contact signal.
( Both voltage and no-votage signals are compatible with pulse input. Set DIP
switch 2-2 to ON. A pulse signal duration of 200 ms or more is needed. )
Output terminal during Lossnay unit operation. ( uncharged a-contact signal
output .)
Contact point rating:
2A/240V AC
Within 2A/24V DC
Output terminal during Lossnay unit malfunction. ( uncharged a-contact sig-
nal output. )
Contact point rating:
1A/240V AC
Within 1A/24V DC
Lossnay
up to 15
Lossnay units
Power
supply
Lossnay
Remote
controller
PZ-41SLB-E
Lossnay
Specification
Air
conditioner
Power supply
Air conditioner
remote controller
Set to "Main"
Set to "Sub"
Page
128/130
131/132
131/133
132 to 133