7. Cable Installation of the M-NET

7.1
Precautions When Installing Wiring.
1. When routing transmission cable outside of the unit, position it 5 cm or more away
cable for the power supply so that it will not pick up electrical noise. ( Never use multi-
core cable or place the transmission cable in the same conduit as the power supply
cable. )
2. Never connect the power cable to the terminal block for the transmission cable. This
erroneous connection will burn out the circuit board.
3. Always use 2-core cable for the transmission cable. Routing this transmission cable
with the transmission cable from another system on the same multi-core cable will
result in erroneous sending and receiving of signals which will cause misoperation.