52 Standard Commissioning Process
Note: If the error information like below, please new a folder named temp in drive C.
Waiting nearly 25 seconds, programming successfully finished. Press any key to exit.
Turn off the control power.
Remove the XILINX platform cable USB II.
Loading the IO controller (AC500eco) software
Save the following files and folders to the SD card (MC502) root folder. Files can be
found in the loading package (folder \04_IOController SW).
Note: Only MC502 SD card can be used. This is not the same SD card which is plugged
into the BCU.
Switch off the control power.
Install SD card adapter (MC503) into CPU PM55X.
Inset SD memory card (MC502) into adapter MC503.