ABB ACS580MV Commissioning Manual page 114

200kw to 6300 kw,3.3kv to 11 kv
Hide thumbs Also See for ACS580MV:
Table of Contents

Advertisement

114 Option
Drive parameter
16.19 DIO3 function
16.21 DIO3 output
source
16.24 DIO4 function
16.26 DIO4 output
source
85.21 Bypass
contactor control
85.22 Contactor
control signal
Set MAU PLC parameters.
If more than one motors are to be sync to mains, marshalling PLC (optional) is used. It
provides parameters, events and IO signals interface to user. Web visualization is used as
interface of marshalling PLC.
Requirements for commissioning PC
1. In order to access PLC, user's computer has to meet below conditions.
Operating system: Windows NT/2000/XP/7/10, Windows CE, Linux, RTE.
A Web-Browser (IE-Explorer or Netscape)
JavaScript is installed on PC. The Java.exe installation could be downloaded from the
official website
https://www.java.com/en/
2. IP address and Subnet mask setting
Connect Marshalling PLC and PC with ethernet cable.
Set Marshalling PLC (optional) and Panel (optional) as below table.
Marshalling PLC
IP address
192.168.0.10
Subnet mask
255.255.255.0
set the PC IP address in the same segment, e.g. 192.168.0.13, and with same Subnet
mask.
Setting
Description
Output
Select DIO3 as output
P 85.2.14
Inductor bypass contactor close command signal is from
SBU function SW bit 14
Output
Select the DIO4 as the output
P 85.2.15
Inductor bypass contactor open command signal is from
SBU function SW bit 15
Enabled
Enable inductor bypass contactor control
Pulse signal
Inductor bypass contact is using pulse signal for control
Panel (CP610)
192.168.0.11
255.255.255.0