No.F002 Fire Extinguishing System Conceptual Diagram 1
+
Technical requirements:
1.
All fire extinguishing signal cables are red (BOM number: 25030029) and black (BOM number: 25030073) cables with naked crimping single-wire cord end terminals (BOM number: 14170214). The red cable is positive and the black cable is
negative. The pneumatic switch, warning signs, and fire alarm bell each has two wiring terminals that connect to two wires. The fire alarm bell is polarity insensitive. For details, see the diagram.
2. Connect a 10 K terminal resistor to each of the last the fire alarm sounder and fire alarm horn/strobe in parallel.
3. Connect cables to the smoke detector and heat detector by referring to the diagram. Connect a 6.8 K terminal resistor to the last smoke and heat detectors in parallel.
4. Connect the emergency abort button and pneumatic switch to a 6.8 K terminal resistor in parallel, and to a 470 ohm resistor in serial. Connect an electrical actuator to a 1N4004 diode in parallel.
5. Alarm signals are reported to the monitoring system over shielded straight-through network cables. The connection definitions are as follows: LOCAL FIRE, FIRE RELAY, and FAULT RELAY. The signal cables connect
to the ECC over dry contacts.
6. Attach cable labels to all cables connected to the extinguishant control panel and wiring terminals on electrical actuators and pneumatic switches. See the label table for the label content. Cable direction labels must be
arranged neatly in the same direction. Cables must be bound neatly, with cable ties in the same direction. (Labels are printed on label paper with the BOM number 29041061, attached on cable ties with the BOM number
21200708, and bound to corresponding cables.)
Terminal Resistor
Terminal Resistor
6.8K
6.8K
S
S
Terminal Resistor
10K
Fire Alarm Bell-A1
1
2
3
4
3
4
B
B
Z
Z
Z
Z
1
1
2
2
red
black
red
black
red
black
10K
-
E
+
+
- +
-
+
- +
- +
- +
ROV
SIL
AL
FLT RST
-
AUX
S1
S2
ZONE 1 ZONE 2
REMOTE
DATA
POWER
CONTROL
STATUS UNITS
Data cable Power cable Connect the first
Connect
stage alarm to
smoke
Connect heat
the fire alarm
detector in
detector in
bell.
detection zone
detection zone
1
2
Horn Strobes
-A2
- + +
Warning Signs-A1
I/P
I/P
2WIRE
SILENCE
SILENCE
COMM+ LEV1 LEV2
COMM+LEV1 LEV2
2WIRE
pneumatic switch-B1
Extinguishant Abort Button
NC
-A1
C
NO
2
4
6.8K
1
3
1
2
3
4
2
2
1
4
1
2
1
2
N
N
D
D
H
H
P
P
S
S
6.8K
S
S
6.8K
6.8K
black
red
black
red
black
red
red
black
+
-
+
-
+
-
+
-
+
-
+
-
+
-
NC
C
NO
NC
C
NO
ZONE 3
2ND
1ST
2ND
MODE
MAN
HOLD
REL
EXTING
SOUNDER
STAGE
STAGE
SELECT
RELEASE
PRESS
SWITCH
Connect the
Connect the pressure
emergency
Connect the second stage
signal to the pneumatic
abort port to
switch.
Connect the electrical
alarm to the horn strobes and
the extinguishant
actuator drive signal to the
warning signs.
abort button.
electrical actuator.
Horn Strobes
-A1
Terminal Resistor
10K
- + +
To Monitoring system
Electrical Actuator-B1
brown & white
green
green
green
brown & white
brown & white
6.8K
+
-
NO
C
NO NC
C
NO
NC
C
NO
NC
C
LOW
EXTRACT
FAULT
LOCAL
FIRE
PRESS
RELAY
FIRE
RELAY
SWITCH
Connect the gas release
Connect the fire alarm
Connect the fault signal
signal output (NO) to the
output (NO) to the
signal output (NO) to the
collector of the monitoring
collector of the monitoring
collector of the monitoring
system.
system.
system.