No.P012 Inverter AC and DC Input Wiring Diagram
Cable No.
1
2
/
1
2
/
Cables are reserved here
and installed onsite.
Cable Relation Table
INPUT
OUTPUT
Container
From Device
Container
Main PDB QF10
Inverter-B1 AC Input
Main PDB QF11
Inverter-B2 AC Input
A1
B1
/
Rectifier Cabinet
Inverter-B1 DC Input
F17
Inverter-B2 DC Input
A1
Rectifier Cabinet F18
B1
/
Breaker
Power System
Huawei Part Description
To Device
L
ElectronicElectric Cable
-300V/500V-60227 IEC
N
53(RVV)-3x1.5mm^2-
16A/1P
Black(3 Cores: Brown, Blue,
Yellow/Green), 19.5
A,Outdoor Cable,CCC,CE
PE
/
+
Electronic|Electric Cable
-600V/1000V-ZA-RVV-3x6
mm^2- Black(3 Cores:
/
Yellow/Green),46A,Outdoor
-
/
Cables are reserved here
and installed onsite.
L, N, and PE are
distinguished by brown,
blue, and yellow and green
heat shrink tubing.
Terminal Relation Table
Terminal Spec From
Terminal Spec From
Part 1
Part 2
14170214
14170214
25030398
Tube-1.5mm
Tube-1.5mm
14170014
14170014
OT-1.5mm -M6
OT-1.5mm -M6
14170014
14170014
OT-1.5mm -M6
OT-1.5mm -M6
14110065
14110065
Tube-6mm
Tube-6mm
25031888
Brown, Blue,
Cable,CE
14110065
14110065
Tube-6mm
Tube-6mm